IEC 61000-4-11: The Inrush Requirement That Disqualifies Most AC Sources
Standards & compliance · 3 min read · 21 cited facts
Voltage dip immunity looks like the least demanding test on a compliance schedule. Drop the supply for a defined number of cycles, see whether the equipment stays up. The levels are modest and the durations are short.
Then you read the generator requirements and discover why a general-purpose programmable source usually cannot run it.
The test levels
| Parameter | Value | Clause |
|---|---|---|
| Dips, Class 2 | 0%/½ cycle, 0%/1 cycle, 70%/25 (50 Hz) or 30 (60 Hz) cycles | 61000-4-11 Table 1 |
| Dips, Class 3 | adds 40%/10–12 cycles and 80%/250–300 cycles | 61000-4-11 Table 1 |
| Interruptions | 0% for 250/300 cycles | 61000-4-11 Table 2 |
The requirement that actually decides the instrument
| Parameter | Value | Clause |
|---|---|---|
| Generator rise/fall | 1–5 µs | 61000-4-11 §6 |
| Peak inrush drive | 500 A (220–240 V) / 250 A (100–120 V) | 61000-4-11 §6 |
Edges in microseconds, not milliseconds
Rise and fall between one and five microseconds is far faster than most programmable sources slew. That is deliberate: the standard is describing what a real distribution fault looks like, and a gentle transition would let equipment ride through a disturbance it should not survive.
Phase-of-dip control changes the answer
Where in the AC cycle the dip begins materially alters what the device experiences — a dip starting at a voltage zero-crossing is a different event from one starting at the peak. The standard expects this to be controllable, which means it has to be a programmable parameter rather than whatever the source happened to do.
Above 16 A per phase you are in a different standard
IEC 61000-4-11 applies to equipment drawing up to 16 A per phase. Larger equipment falls under IEC 61000-4-34, which carries the same intent at a scale that changes the generator entirely. Confirm which one your product falls under before you specify anything, because the answer moves the budget.
Specifying a dip-immunity bench?
Tell us your equipment's per-phase current and class. The inrush requirement will decide most of the rest.
Talk to an engineerRelated
More on standards & compliance
- IEC 61000-4-13: Synthesising Distortion on Command — and the Tables We Do Not Reprint4 min · 20 facts
- IEC 61000-4-29 Edition 2.0: One DC Supply as the Whole Generator4 min · 39 facts
- MIL-STD-1399 Testing: Your Contract May Cite a Cancelled Revision4 min · 23 facts
- MIL-STD-461G CS101: Ripple Injection on Power Leads, Step by Step3 min · 16 facts
