IEEE 1547.1 Grid-Tied Inverter Conformance

Four-quadrant regenerative grid simulator covering 0–1.2 pu, 56–66 Hz, with programmable ROCOF to ≥3 Hz/s, phase-jump capability and sub-cycle event timing.

This standard turns on

  • grid emulation
  • ride-through envelopes
  • anti-islanding
  • ROCOF

And says nothing about

  • 400 Hz
  • semiconductor reliability
  • automotive voltage classes

Cited limits

Every value carries the clause, table or figure it comes from.

ParameterValueClause
Voltage trip defaultsOV2 1.20 pu/0.16 s; OV1 1.10 pu/2 s; UV1 0.88 pu/2–21 s; UV2 0.50 pu/0.16–2 sIEEE 1547-2018
Frequency trip62.0 Hz/0.16 s; 61.2 Hz/300 s; 58.5 Hz/300 s; 56.5 Hz/0.16 sIEEE 1547-2018
Ride-through Cat IIIcontinuous 0.88–1.10 pu; mandatory 0.50–0.88 pu; cease >1.20 puIEEE 1547-2018
ROCOF Cat III3.0 Hz/sIEEE 1547-2018 Table 21
Unintentional islandingparallel RLC at Qf = 1.0; cease to energize within 2 sIEEE 1547.1-2020